CABLE SUPPORT SYSTEM - TIS-STRUT - T1001
COLUMN LOADING - T1001

Unbraced Height Maximum Allowable Load at Slot Face Maximum Column Load Applied at C.G.
K = 0.65 K = 0.80 K = 1.0 K = 1.2
In Lbs Lbs Lbs Lbs Lbs
24
36
6.430
6.230
25.060
24.000
24.620
23.050
23.900
21.570
23.050
19.890
48
60
5.950
5.620
22.590
20.890
21.030
18.690
18.690
15.540
16.170
12.400
72
84
5.240
4.830
18.990
16.970
16.170
13.640
12.400
9.470
8.960
6.580
96
108
4.390
3.930
14.900
12.860
11.200
8.960
7.250
5.730
5.040
3.980
120 3.510 10.910 7.250 4.640 **
BEAM LOADING - T1001

Span Maximum Allowable Uniform Load Deflection at Uniform Load Uniform Loading at Deflection
Span/180 Span/240 Span/360
In Lbs In Lbs Lbs Lbs
24
36
3.130*
3.130*
0.03
0.07
3.130*
3.130*
3.130*
3.130*
3.130*
3.130*
48
60
2.400
1.920
0.13
0.20
2.400
1.920
2.400
1.920
2.400
1.630
72
84
1.600
1.370
0.28
0.39
1.600
1.370
1.600
1.240
1.130
830
96
108
1.200
1.070
0.50
0.64
1.200
1.000
950
750
640
500
120
144
960
800
0.79
1.13
810
560
610
420
410
280
168
192
690
600
1.54
2.01
410
320
310
240
210
160
216
240
530
480
2.55
3.15
250
200
190
150
130
100
Product Info
Weight : 380 Lbs/100 Ft (566 kg/100 m)
Wt/100 Ft : 380 Lbs (566 kg/100 m)
Allowable Moment T1001 : 14.390 In-Lbs (1.630 N•m)
12 Gauge Nominal Thickness 2.5 mm
Dimension Tolerance : ± 1.0 mm